Customization: | Available |
---|---|
Type: | Lead-Acid Batteries |
Usage: | UPS, Electric Power, Lighting, Boat, Solar, Telecom |
Still deciding? Get samples of US$ 93/Piece
Request Sample
|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Battery Model | HX12-100 / HXG12-100 | |||
Capacity (25ºC) |
10HR (10.8V) | 5HR (10.5V) | 1HR (9.6V) | / |
100.0Ah | 76.0Ah | 60.9Ah | / | |
Dimension | Length | Width | Height | Total Height |
330±2mm (12.99inch) | 171±2mm (6.73inch) | 214±2mm (8.43inch) | 220±2mm (8.66inch) | |
Approx. Weight | 29.5kg (64.4lbs) ±5% | |||
Terminal Type | F14 | |||
Internal Resistance (Fully charged, 25ºC) |
Approx. 4.5mΩ | |||
Capacity affected by temperature (20HR) |
40ºC | 25ºC | 0ºC | -15ºC |
102% | 100% | 85% | 65% | |
Self-discharge | 3 months | 6 months | 12 months | / |
Remaining Capacity: 91% | Remaining Capacity: 82% | Remaining Capacity: 65% | / | |
Nominal Operating Temperature | 25ºC ± 3ºC (77ºF±5ºF) | |||
Operating Temerature Range | Discharge | Charge | Storage | / |
-15ºC~50ºC (5ºF~122ºF) |
-10ºC~50ºC (14ºF~122ºF) |
-20ºC~50ºC (-4ºF~122ºF) |
/ |
|
Charging Voltage (25ºC) | Floating Charging | Cyclic Charging | ||
13.60 to 13.80V Temperature compensation: -18mV/ºC |
14.50 to 15.00V Temperature compensation: -30mV/ºC |
|||
Maximum Charging Current | 30A | |||
Maximum Discharge Current | 800A (5 sec.) | |||
Designed Floating Life (20ºC) |
10 years / 12 years |