Type: | Lead-Acid Batteries |
---|---|
Usage: | UPS, Electric Power, Solar, Telecom |
Nominal Voltage: | 2V |
Discharge Rate: | Low Discharge Rate |
Shape: | Square Battery |
Installation: | Packaged |
Samples: |
---|
Customization: |
---|
Suppliers with verified business licenses
Battery Model | OPzS2-600 | |||
Capacity (25ºC) |
100HR (1.85V) | 10HR (1.80V) | 3HR(1.75V) | / |
720.0Ah | 600.0Ah | 471Ah | / | |
Dimension | Length | Width | Height | Total Height |
206±2mm (8.11inch) | 145±1mm (5.71inch) | 646±3mm (25.43inch) | 701±3mm (27.60inch) | |
Approx. Weight | wet 49kg (108lbs) ±4% | |||
Terminal Type | F12 | |||
Internal Resistance (Fully charged, 25ºC) |
Approx. 0.45mΩ | |||
Capacity affected by temperature (20HR) |
40ºC | 25ºC | 0ºC | -15ºC |
102% | 100% | 85% | 65% | |
Self-discharge | 3 months | 6 months | 12 months | / |
Remaining Capacity: 91% | Remaining Capacity: 82% | Remaining Capacity: 65% | / | |
Nominal Operating Temperature | 25ºC ± 3ºC (77ºF±5ºF) | |||
Operating Temerature Range | Discharge | Charge | Storage | / |
-15ºC~50ºC (5ºF~122ºF) |
-10ºC~50ºC (14ºF~122ºF) |
-20ºC~50ºC (-4ºF~122ºF) |
/ |
|
Charging Voltage (25ºC) | Floating Charging | Cyclic Charging | ||
2.23 to 2.25V Temperature compensation: -3mV/ºC |
2.35 to 2.40V Temperature compensation: -5mV/ºC |
|||
Maximum Charging Current | 120A | |||
Maximum Discharge Current | 2400A (5 sec.) | |||
Designed Floating Life (20ºC) |
20 years |
Suppliers with verified business licenses