Customization: | Available |
---|---|
Type: | Lead-Acid Batteries |
Usage: | Bus, UPS, Electric Power, Boat |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Battery Model | HX12-200 / HXG12-200 | |||
Capacity (25ºC) |
10HR (10.5V) | 5HR (10.5V) | 1HR (9.6V) | / |
200.0Ah | 176.0Ah | 124.0Ah | / | |
Dimension | Length | Width | Height | Total Height |
522±2mm (20.55inch) | 238±2mm (9.37inch) | 218±2mm (8.58inch) | 221±2mm (8.70inch) | |
Approx. Weight | 59.5kg (94.8lbs) ±5% | |||
Terminal Type | F13 | |||
Internal Resistance (Fully charged, 25ºC) |
Approx. 3mΩ | |||
Capacity affected by temperature (20HR) |
40ºC | 25ºC | 0ºC | -15ºC |
102% | 100% | 85% | 65% | |
Self-discharge | 3 months | 6 months | 12 months | / |
Remaining Capacity: 91% | Remaining Capacity: 82% | Remaining Capacity: 65% | / | |
Nominal Operating Temperature | 25ºC ± 3ºC (77ºF±5ºF) | |||
Operating Temerature Range | Discharge | Charge | Storage | / |
-15ºC~50ºC (5ºF~122ºF) |
-10ºC~50ºC (14ºF~122ºF) |
-20ºC~50ºC (-4ºF~122ºF) |
/ |
|
Charging Voltage (25ºC) | Floating Charging | Cyclic Charging | ||
13.60 to 13.80V Temperature compensation: -18mV/ºC |
14.50 to 15.00V Temperature compensation: -30mV/ºC |
|||
Maximum Charging Current | 60A | |||
Maximum Discharge Current | 1600A (5 sec.) | |||
Designed Floating Life (20ºC) |
10 years / 12 years |
Please contact us for any other customization needs.
We use ISO 9001, ISO 14001, ISO 45001 quality systems for quality control. We have incoming quality control (IQC) department to test, production quality control (PQC) department, outgoing quality control (OQC) department to confirm that no defective cells come out of the factory.